6.4 START INHIBIT/RESET
NOTE:
NOTE:NOTE:
NOTE:
If a digital input configur
If a digital input configurIf a digital input configur
If a digital input configured to
ed to ed to
ed to
panel lock
panel lockpanel lock
panel lock
is active,
is active, is active,
is active, changing module modes will
changing module modes will changing module modes will
changing module modes will
not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
not be possible. Viewing the instruments and event logs is NOT affected by panel lock. not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
not be possible. Viewing the instruments and event logs is NOT affected by panel lock.
State Inhibit mode is activated by pressing the button.
In START INHIBIT
‘ ’
mode, the module will remove S2 from load (if necessary) and remove the
start signal given to the generator controller (if S2 is configured as a generator and it is running).
If S2 is configured as a generator and it does not stop after the cooling down time, the FAIL TO STOP
alarm is activated (subject to if the FAIL TO STOP timer si enabled and its duration). To detect the
generator (S2) is at rest the following must occur:
• S2 Frequency must be zero.
• S2 Voltage must be zero.
Any latched alarms that have been cleared will be reset when START INHIBIT
‘ ’
mode is entered.
S2 will not be placed on load (or started if configured as a generator) when in START INHIBIT
‘ ’
mode. If remote start signals are given, the input is ignored until AUTO
‘ ’
mode is entered.