Scheduler
69
8 SCHEDULER
The controller contains an inbuilt exercise run scheduler, capable of automatically starting and
stopping the set. Up to 16 scheduled start/stop sequences can be configured in banks of 8 to either
repeat on a 7-day or 28-day cycle.
Scheduled runs may be on load or off load depending upon module configuration.
Example
Screen capture from
DSE Configuration
Suite Software
showing the
configuration of the
Exercise Scheduler.
In this example the
set will start at 09:00
on the first Monday of
each month and run
for 5 hours, then start
at 13:30 on every
Tuesday and run for
30 minutes.
8.1 STOP MODE
• Scheduled runs will not occur when the module is in START INHIBIT
‘ ’
mode.
8.2 MANUAL MODE
• Scheduled runs will not occur when the module is in MANUAL
‘ ’
mode.
• Activation of a Scheduled Run ‘On Load’ when the module is operating OFF LOAD in Manual
mode will have no effect, the set continues to run OFF LOAD
8.3 AUTO MODE
• Scheduled runs will operate ONLY if the module is in AUTO
‘ ’
mode with no Electrical Trip
alarm present.
• If the module is in START INHIBIT
‘ ’
or MANUAL
‘ ’
mode when a scheduled run
begins, S2 will not be started (if configured as generator). However, if the module is moved
into AUTO
‘ ’
mode during a scheduled run, S2 will be called to start.
• Depending upon configuration by the system designer, an external input can be used to inhibit
a scheduled run.
• If S2 is OFF LOAD in AUTO
‘ ’
mode and a scheduled run configured to ‘On Load’ begins,
S2 is placed ON LOAD for the duration of the Schedule.